DN-RVS - Soft starter
Advantages at a glance:
 |
Complete line 8...27000A, 220...1000V |
 |
Heavy duty, fully rated design |
 |
Robust construction |
 |
Superior starting & stopping characteristics |
 |
Comprehensive Motor Protection package |
 |
User friendly |
 |
Maximum ambient temperature: 50° C |
 |
Unique optional features including:
- Motor Insulation Tester
- RS 485 Comm. Modbus / Profibus / TCP-IP
- Thermistor input / Analogue input |
| |
|
ESCOSTART Soft starters Technical data
| Type DN-RVS... |
8 |
17 |
31 |
44 |
58 |
72 |
105 |
145 |
170 |
210 |
310 |
390 |
460 |
580 |
820 |
| Rated Output Current (A) |
8 |
17 |
31 |
44 |
58 |
72 |
105 |
145 |
170 |
210 |
310 |
390 |
460 |
580 |
820 |
Rated Motor
Power
(kW) at
400 V |
4 |
7,5 |
15 |
22 |
30 |
37 |
55 |
75 |
90 |
110 |
160 |
200 |
250 |
315 |
450 |
| Dimensions |
A |
B |
C |
D |
| Width (mm) |
153 |
274 |
590 |
623 |
| Height (mm) |
310 |
370 |
500 |
660 |
| Height (mm) |
170 |
217 |
279 |
292 |
290 |
| Weight (kg) |
4,5 |
6,8 |
7,5 |
15 |
31 |
65 |
| Protection |
IP 20 |
IP 00 |
| Supply Voltage |
3 x 380 ... 440V, -15 ... +10 %; 50/60Hz ± 4 %, special voltage on request |
| Control
Connections |
switching contacts |
| Current Limit |
100 ... 400% of rated motor current |
| Max. Starts/h |
4 starts/h at maximum load; up to 60 starts/h at reduced load |
| Acceleration Time |
1...30 s |
| Deceleration Time |
1...30 s |
| Initial Voltage |
10 ... 50% of supply voltage |
Protective
Function
LED Indication |
electronic overload tripping, phase loss detection, overtemperature |
| Relay Output |
3 relays: operation, fault indication, end of acceleration (1S 8A, 250V AC) |
Ambient Air
Temperature |
-10°C ... +50°C |
| Conformity |
CE, UL, cUL, Loyd’s, GL (on request: GOST, CCC, Rina, etc.) |
|